The NSP1-C40 AC Surge Protective Device 4 Pole is designed to safeguard electrical installations and sensitive equipment from high-energy transient surges caused by lightning and power switching events. It effectively diverts surge currents to ground, preventing costly damage and ensuring uninterrupted operation.
Built for three-phase (3P+N) electrical systems, the NSP1-C40 features a 385V AC maximum continuous operating voltage (Uc), 20kA nominal discharge current (In), and 40kA maximum discharge current (Imax), delivering reliable and long-lasting surge protection.
The modular DIN rail design enables quick installation in distribution boards and control panels, while the built-in visual status indicator makes maintenance simple by displaying green for normal operation and red when replacement is required.
Manufactured according to IEC 61643-11 standards, the NSP1-C40 is an ideal solution for protecting industrial machinery, commercial buildings, renewable energy systems, and critical electrical infrastructure.
Key Features
- Model: NSP1-C40
- 4 Pole AC Surge Protective Device
- Type 2 SPD
- Suitable for Three-Phase (3P+N) Systems
- Maximum Continuous Operating Voltage (Uc): 385V AC
- Nominal Discharge Current (In): 20kA
- Maximum Discharge Current (Imax): 40kA
- Fast response to lightning and switching surges
- Green/Red visual status indicator
- DIN Rail mounting
- Compact modular construction
- Long service life
- Low maintenance
- IEC 61643-11 compliant
Applications
- Three-Phase Distribution Boards
- Commercial Buildings
- Industrial Plants
- Manufacturing Facilities
- Data Centers
- Shopping Malls
- Hospitals
- Office Buildings
- Power Distribution Panels
- HVAC Systems
- Automation Panels
- Electrical Switchboards
Technical Specifications
| Specification | Details |
|---|---|
| Model | NSP1-C40 |
| Product Type | AC Surge Protective Device |
| SPD Type | Type 2 |
| Poles | 4 Pole |
| System | Three Phase (3P+N) |
| Maximum Continuous Operating Voltage (Uc) | 385V AC |
| Nominal Discharge Current (In) | 20kA |
| Maximum Discharge Current (Imax) | 40kA |
| Voltage Protection Level (Up) | ≤1.8kV |
| Mounting | DIN Rail |
| Standard | IEC 61643-11 |




Reviews